When the NS LED is flashing in green
When the NS LED is flashing in green, check the following.
Check item
Have the following buffer memory values been checked?
• Class1 communication status 'Data link status' (Un\G6030 to Un\G6031)
• Connection behavior error status 'Class1 connection 1 to 32 error code'
(Un\G6262 to Un\G6293)
Has communication start processing been performed correctly with 'EtherNet/
IP communication start request' (Un\G37.b0)?
When the NS LED is flashing in red
When the NS LED is flashing in red, check the following.
Check item
Is the EtherNet/IP device connected correctly?
When the SD/RD LED does not turn on during data communication
When the SD/RD LED does not turn on during data communication, check the following.
Check item
Is the ERROR LED on or flashing?
Is the Ethernet cable connected correctly?
Are the parameter settings correct?
Are there any errors in the program?
If the above actions do not solve the problem, perform the hardware test to check for FX5-ENET/IP failure. (Page 119
Hardware Test)
10 TROUBLESHOOTING
108
10.1 Checking with LEDs
Action
• Check whether the buffer memory values are normal.
• Take the action corresponding to the value of 'Class1 connection 1 to 32
error code' (Un\G6262 to Un\G6325). (Page 149 Connection behavior
error status (Un\G6262 to Un\G6293))
• Check that 'EtherNet/IP communication start request' (Un\G37.b0) is on.
• If 'EtherNet/IP data link continuation specification' (Un\G5004) is set to "16:
continue EtherNet/IP communication" , turn 'EtherNet/IP communication
start request' (Un\G37.b0) on again.
Action
• Check whether the operating status of the EtherNet/IP device is normal.
(Page 121 EtherNet/IP communications cannot be performed)
• Check for errors in the line status.
• The line may be busy, so retry at a later time.
Action
Take the actions displayed in the module diagnostics. (Page 109 Module
diagnostics)
• Connect the Ethernet cable again.
• Perform a PING test to check the line status. (Page 118 PING test)
Revise the following items with EtherNet/IP Configuration Tool for FX5-ENET/
IP.
• Model and name of the connected EtherNet/IP device
• IP address of the connected EtherNet/IP device
• Version of the registered EDS file
• 'Check that 'EtherNet/IP communication start request' (Un\G37.b0) is on.
• Check and correct the data communication program.