Item
[Send to Device] button
Continue (500ms)
Messaging
Receive
Status
*1 To perform message communications with products other than the FX5-ENET/IP, refer to the manual of the product used.
*2 This item is displayed when "Advanced Mode" is selected. (Page 56 File)
*3 Large Forward Open is used when the size of data to be sent/received is 512 bytes or more.
*4 Forward Open is used when the size of data to be sent/received is 511 bytes or less.
*5 Due to the restrictions of EtherNet/IP Configuration Tool for FX5-ENET/IP, when the response data exceeds 1410 bytes, the response
data is not displayed and "Status = 58 (0x3A), Status EtherNet/IP = 0 (0x0)" is displayed in "Status".
8 EtherNet/IP Configuration Tool for FX5-ENET/IP
70
8.1 Window Structure
Description
Starts Class3 communications and UCMM communications.
When this check box is selected, Class3 communications and UCMM
communications will be executed repeatedly at intervals of 500 ms.
Selects the communication method.
• Connected: Class3 communications
• Unconnected: UCMM communications
When selecting "Connected", select whether to use "Large Forward
Open".
• Selected: Performs Class3 communications using Large Forward
*3
Open.
• Not selected: Performs Class3 communications using Forward
*4
Open.
Displays the response data from the EtherNet/IP device.
The response data is the data excluding the first four bytes including
the CIP service code and the status code.
Displays the communication result. For details, refer to the manuals of
the EtherNet/IP device.
Setting range
• Selected
• Not selected
(Default: Not selected)
• Connected
• Unconnected
(Default: Unconnected)