Own Node Setting
Set the IP address of the FX5-ENET/IP.
Item
IP Address
IP Address
Setting
Subnet Mask
Default Gateway
Opening Method
*1 When the parameter is written without the IP address setting (blank), the following address is set.
192.168.3.251
Operational Setting
Set the destination alive check conditions for socket communication.
Item
Timer Settings
Change/Set Timer Value
for Data
Communication
Destination Alive Check
Start Interval Timer
Destination Alive Check
Interval Timer
Destination Alive Check
Resend Count
Description
Sets the IP address of the FX5-ENET/IP
Set the class and subnet address of the FX5-ENET/IP to the same settings
as those of the EtherNet/IP devices that communicate with the FX5-ENET/
IP. Contact the network administrator before setting the IP address.
Sets the subnet mask of the FX5-ENET/IP.
When setting the IP address of the default gateway and performing
communication with an EtherNet/IP device in another network through a
router, set the subnet mask pattern of the default gateway. All the devices in
the same subnetwork should have a common subnet mask. The subnet
mask setting is not required for communication in a single network.
Sets the default gateway of the FX5-ENET/IP.
Set the IP address of the relay device (default gateway) to access the
EtherNet/IP device in another network.
Set a value that satisfies the following conditions as the IP address of the
default gateway.
• The class of the IP address is A, B, or C.
• The subnet address of the default gateway is the same as that of the
FX5-ENET/IP.
• The host address part is not a sequence of "0" or "1".
Select how to open a connection.
• Do Not Open by Program: Select this item to perform open processing
and open the connection by the external device. Program for open/close
processing is not required.
• Open by Program: Select this item to perform open/close processing and
open/close the connection by a program.
Description
Select whether to change timer values from the default.
The timer operates with its default value when "No" is selected.
Set the time interval between the reception of the last message from the
external device and the start of alive check.
Set the time interval for performing alive check again when no response is
returned from the external device of alive check target.
Set the number of times to perform alive check when no response is
returned from the external device of alive check target.
*1
7 PARAMETER SETTINGS
Setting range
• Blank
• 0.0.0.1 to 223.255.255.254
(Default: Blank)
• Blank
• 0.0.0.1 to 255.255.255.255
(Default: Blank)
• Blank
• 0.0.0.1 to 223.255.255.254
(Default: Blank)
• Do Not Open by Program
• Open by Program
(Default: Do Not Open by
Program)
Setting range
• No
• Yes
(Default: No)
• Unit [s]: 1 to 16383
• Unit [ms]: 100 to 16383000
(Default: 600 s)
• Unit [s]: 1 to 16383
• Unit [ms]: 100 to 16383000
(Default: 10 s)
1 to 32767
(Default: 3 Times)
51