Apparatus control APC

11.2.1

Application

The apparatus control is a function for control and supervising of circuit breakers,
disconnectors, and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck, operator
place selection and external or internal blockings.
Figure
69
commands. Commands to an apparatus can be initiated from the Control Centre (CC), the
station HMI or the local HMI on the IED front.
IED
Apparatus
Control
I/O
IEC08000227 V1 EN-US
Figure 69: Overview of the apparatus control functions
Features in the apparatus control function:
Operation of primary apparatuses
Select-Execute principle to give high security
Selection and reservation function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Application manual
The complete apparatus control function is not included in this product, and
the information below is included for understanding of the principle for the use
of QCBAY, LOCREM, LOCREMCTRL, SCILO, SCSWI, SXCBR.
gives an overview from what places the apparatus control function receive
Station HMI
Local
HMI
IED
Apparatus
Control
breakers disconnectors earthing switches