ABB RELION 650 Series Applications Manual page 208

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 13
Monitoring
IGenZeroDb : Minimum level of current in % of IBase used as indication of zero current (zero
point clamping). If measured value is below
UAmpCompY : Amplitude compensation to calibrate voltage measurements at Y% of Ur, where
Y is equal to 5, 30 or 100.
IAmpCompY : Amplitude compensation to calibrate current measurements at Y% of Ir, where Y
is equal to 5, 30 or 100.
IAngCompY : Angle compensation to calibrate angle measurements at Y% of Ir, where Y is
equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase current measurement
(CMMXU).
IAmpCompY : Amplitude compensation to calibrate current measurements at Y% of Ir, where Y
is equal to 5, 30 or 100.
IAngCompY : Angle compensation to calibrate angle measurements at Y% of Ir, where Y is
equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase voltage measurement
(VMMXU).
UAmpCompY : Amplitude compensation to calibrate voltage measurements at Y% of Ur, where
Y is equal to 5, 30 or 100.
UAngCompY : Angle compensation to calibrate angle measurements at Y% of Ur, where Y is
equal to 5, 30 or 100.
The following general settings can be set for all monitored quantities included in the
functions (, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X in setting names below equals S, P,
Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2, 3I0, U1, U2 or 3U0.
Xmin : Minimum value for analog signal X set directly in applicable measuring unit.
Xmax : Maximum value for analog signal X.
XZeroDb : Zero point clamping. A signal value less than XZeroDb is forced to zero.
Observe the related zero point clamping settings in Setting group N for (
IGenZeroDb ). If measured value is below UGenZeroDb and/or IGenZeroDb calculated S, P, Q
and PF will be zero and these settings will override
XRepTyp : Reporting type. Cyclic ( Cyclic ), amplitude deadband ( Dead band ) or integral
deadband (
XDbRepInt : Reporting deadband setting. Cyclic reporting is the setting value and is reporting
interval in seconds. Amplitude deadband is the setting value in % of measuring range. Integral
deadband setting is the integral area, that is, measured value in % of measuring range
multiplied by the time between two measured values.
XHiHiLim : High-high limit. Set in applicable measuring unit.
XHiLim : High limit.
XLowLim : Low limit.
XLowLowLim : Low-low limit.
XLimHyst : Hysteresis value in % of range and is common for all limits.
202
Int deadband ). The reporting interval is controlled by the parameter XDbRepInt .
IGenZeroDb calculated S, P, Q and PF will be zero.
XZeroDb .
1MRK 504 158-UEN A
UGenZeroDb and
Application manual