created from any available signal in the IED that is connected to the Event function (EVENT).
The EVENT function block is used for LON and SPA communication.
Analog and double indication values are also transferred through the EVENT function.
13.5.3

Setting guidelines

The parameters for the Event (EVENT) function are set via the local HMI or PCM600.
EventMask (Ch_1 - 16)
The inputs can be set individually as:
NoEvents
OnSet , at pick-up of the signal
OnReset , at drop-out of the signal
OnChange , at both pick-up and drop-out of the signal
AutoDetect
LONChannelMask or SPAChannelMask
Definition of which part of the event function block that shall generate events:
Off
Channel 1-8
Channel 9-16
Channel 1-16
MinRepIntVal (1 - 16)
A time interval between cyclic events can be set individually for each input channel. This can be
set between 0 s to 3600 s in steps of 1 s. It should normally be set to 0, that is, no cyclic
communication.
13.6

Disturbance report DRPRDRE

13.6.1

Identification

Function description
Disturbance report
Disturbance report
Disturbance report
Application manual
It is important to set the time interval for cyclic events in an optimized way to
minimize the load on the station bus.
IEC 61850 identification
DRPRDRE
A1RADR - A4RADR
B1RBDR - B8RBDR
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
-
-
-
-
Section 13
Monitoring
IP14841-1 v1
M12811-3 v2
M12811-5 v2
M12811-15 v2
M12811-29 v3
M12811-34 v1
IP14584-1 v2
M16055-1 v7
213

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret650

Table of Contents