Setting Guidelines - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
7.9.3

Setting guidelines

GlobalBaseSel : Selects the global base value group used by the function to define ( IBase ),
UBase ) and ( SBase ).
(
Operation : With the parameter Operation the function can be set On / Off .
Mode : The voltage and current used for the power measurement. The setting possibilities are
shown in table 21.
Table 21:
Set value
L1, L2, L3
Arone
PosSeq
L1L2
L2L3
L3L1
L1
L2
L3
The function has two stages that can be set independently.
With the parameter
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is larger than the set pick up power value Power1(2)
Application manual
Complex power calculation
Mode
OpMode1(2) the function can be set On / Off .
Formula used for complex power calculation
*
*
=
×
+
×
S
U
I
U
I
L
1
L
1
L
2
L
2
EQUATION1697 V1 EN-US
*
=
×
-
×
S
U
I
U
L L
1 2
L
1
L L
2 3
EQUATION1698 V1 EN-US
*
= ×
×
S
3
U
I
PosSeq
PosSeq
EQUATION1699 V1 EN-US
*
*
=
×
-
S
U
(
I
I
)
L L
1 2
L
1
L
2
EQUATION1700 V1 EN-US
*
*
=
×
-
S
U
(
I
I
)
L L
2 3
L
2
L
3
EQUATION1701 V1 EN-US
*
*
=
×
-
S
U
(
I
I
)
L L
3 1
L
3
L
1
EQUATION1702 V1 EN-US
*
= ×
×
S
3
U
I
L
1
L
1
EQUATION1703 V1 EN-US
*
= ×
×
S
3
U
I
L
2
L
2
EQUATION1704 V1 EN-US
*
= ×
×
S
3
U
I
L
3
L
3
EQUATION1705 V1 EN-US
Current protection
SEMOD172150-4 v7
*
+
×
U
I
L
3
L
3
(Equation 66)
*
I
L
3
(Equation 67)
(Equation 68)
(Equation 69)
(Equation 70)
(Equation 71)
(Equation 72)
(Equation 73)
(Equation 74)
Section 7
133