Setting Guidelines; Bay Control (Qcbay) - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
IEC05000120 V2 EN-US
Figure 75: Example overview of the interactions between functions in a typical bay
11.2.3

Setting guidelines

The setting parameters for the apparatus control function are set via the local HMI or PCM600.
11.2.3.1

Bay control (QCBAY)

If the parameter
accepted without any priority.
If the parameter
station and remote level are accepted, when the QCBAY function is in Remote. If set to
command LocSta controls which operator place is accepted when QCBAY is in Remote. If
Application manual
SMPPTRC
(Trip logic)
QCBAY
Operator place
(Bay control)
selection
Res. req.
Res. granted
QCRSV
(Reservation)
Res. req.
Close CB
SMBRREC
(Auto-
reclosure)
Open rel.
Interlocking
Close rel.
function
Open rel.
block
Close rel.
(Not a LN)
Position
Res.
GAPC
granted
(Generic
Automatic
Open/Close
Process
Control)
Open/Close
AllPSTOValid is set to No priority , all originators from local and remote are
RemoteIncStation is set to Yes , commands from IEC 61850-8-1 clients at both
SESRSYN
(Synchrocheck & Synchronizer)
Trip
Synchrocheck
OK
Open cmd
Close cmd
SCSWI
(Switching control)
Position
SCILO
(Interlocking)
SCILO
(Interlocking)
Enable
Enable
open
close
Open cmd
Close cmd
SCSWI
(Switching control)
Position
Section 11
Synchronizing
in progress
SXCBR
(Circuit breaker)
I/O
SXSWI
(Disconnector)
I/O
IEC05000120-2-en.vsd
No , the
Control
M16669-3 v4
M16670-3 v7
171