Setting Guidelines; Generic Communication Function For Double Point Indication Dpgapc; Identification; Application - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
represent it through the single line diagram symbols (or use it in the configuration through the
outputs POS1 and POS2) as well as, a command function (controlled by the PSTO input), giving
switching commands through the CMDPOS12 and CMDPOS21 outputs.
The output POSITION is an integer output, showing the actual position as an integer number 0
– 3.
An example where VSGAPC is configured to switch Autorecloser on–off from a button symbol
on the local HMI is shown in figure76. The I and O buttons on the local HMI are normally used
for on–off operations of the circuit breaker.
INTONE
OFF
ON
IEC07000112 V3 EN-US
Figure 76: Control of Autorecloser from local HMI through Selector mini switch
VSGAPC is also provided with IEC 61850 communication so it can be controlled from SA
system as well.
11.4.3

Setting guidelines

Selector mini switch (VSGAPC) function can generate pulsed or steady commands (by setting
Mode parameter). When pulsed commands are generated, the length of the pulse can be
the
set using the
function block has two control modes (settable through
11.5
Generic communication function for Double Point
indication DPGAPC
11.5.1

Identification

Function description
Generic communication function for
Double Point indication
11.5.2

Application

Generic communication function for Double Point indication (DPGAPC) function block is used
to send double point position indication to other systems, equipment or functions in the
substation through IEC 61850-8-1 or other communication protocols. It is especially intended
to be used in the interlocking station-wide logics. To be able to get the signals into other
systems, equipment or functions, one must use other tools, described in the Engineering
Application manual
VSGAPC
PSTO
IPOS1
IPOS2
NAM_POS1
CMDPOS12
NAM_POS2
CMDPOS21
tPulse parameter. Also, being accessible on the single line diagram (SLD), this
IEC 61850
identification
DPGAPC
INVERTER
INPUT
OUT
SMBRREC
ON
SETON
OFF
IEC07000112-3-en.vsd
CtlModel ): Dir Norm and SBO Enh .
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 11
Control
SEMOD158807-4 v4
SEMOD55384-1 v4
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
SEMOD55391-5 v8
175