Section 7
Current protection
IEC05000492 V2 EN-US
Figure 52: Step 1 fault calculation 1
This calculation gives the current fed to the protection: 3I
To assure that step 1, selectivity to other earth-fault protections in the network a short delay is
selected. Normally, a delay in the range 0.3 – 0.4 s is appropriate. To assure selectivity to line
faults, tripped after a delay (typically distance protection zone 2) of about 0.5 s the current
setting must be set so high so that such faults does not cause unwanted step 1 trip. Therefore,
a fault calculation as shown in figure
IEC05000493 V2 EN-US
Figure 53: Step 1 fault calculation 1
The fault is located at the borderline between instantaneous and delayed operation of the line
protection, such as Distance protection or line residual overcurrent protection. This calculation
gives the current fed to the protection: 3I
The setting of step 1 can be chosen within the interval shown in equation 34.