1MRK 504 158-UEN A
12.13.2
Application
The function gives the possibility to monitor the level of integer values in the system relative
to each other or to a fixed value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.
12.13.3
Setting guidelines
For proper operation of comparison the set value should be set within the range of ± 2 ×10
Setting procedure on the IED:
EnaAbs : This setting is used to select the comparison type between signed and absolute
values.
Absolute : The function will do absolute comparison between input and reference value
•
Signed : The function will do signed comparison between input and reference value
•
RefSource : This setting is used to select the reference source between input and setting for
comparison.
REF : The function will take reference value from input REF
•
SetValue : The function will take reference value from setting SetValue
•
SetValue : This setting is used to set the reference value for comparison when setting
RefSource is selected as SetValue .
12.13.4
Setting example
For absolute comparison between inputs:
Set the
Set the
Similarly for Signed comparison between inputs
Set the
Set the
For absolute comparison between input and setting
Set the
Set the
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
Set the
SetValue shall be set between -2000000000 to 2000000000.
Application manual
EnaAbs = 1
RefSource = 1
EnaAbs = 0
RefSource = 1
EnaAbs = 1
RefSource = 0
EnaAbs = 0
RefSource = 0
Section 12
Logic
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v1
9
.
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v1
195