ABB RELION 650 Series Applications Manual page 56

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 4
Analog inputs
U
=
3
Uo
EQUATION1926 V1 EN-US
The primary rated voltage of such VT is always equal to UPh-E Therefore, three series
connected VT secondary windings will give the secondary voltage equal only to one individual
VT secondary winding rating. Thus the secondary windings of such open delta VTs quite often
has a secondary rated voltage close to rated phase-to-phase VT secondary voltage, that is,
115V or 115/√3V as in this particular example. Figure
are needed to make this measurement available to the built-in protection and control
functions within the IED.
138
138
kV
3
115
V
3
138
kV
3
115
V
3
IEC06000602 V4 EN-US
Figure 19: Open delta connected VT in low impedance or solidly earthed power system
50
-
=
Ph Ph
U
-
Ph E
3
L1
L2
L3
kV
3
115
V
3
19
IED
2
3
1
+3Uo
gives an overview of the actions which
SMAI2
BLOCK
REVROT
# Not Used
^GRP2L1
# Not Used
^GRP2L2
^GRP2L3
# Not Used
^GRP2N
4
IEC06000602-4-en.vsdx
1MRK 504 158-UEN A
(Equation 7)
5
AI3P
AI1
AI2
AI3
AI4
AIN
Application manual