Section 6
Differential protection
REFPDIF
IdN/I
IEC09000109-4-EN V2 EN-US
Figure 31:
6.2.2.2
Transformer winding, earthed through zig-zag earthing transformer
A common application is for low reactance earthed transformer where the earthing is through
separate zig-zag earthing transformers. The fault current is then limited to typical 800 to 2000
A for each transformer. The connection for this application is shown in figure 32.
80
I3PW1CT1
I3P
Connection of the low impedance Restricted earth-fault function REFPDIF for
a directly (solidly) earthed transformer winding
1MRK 504 158-UEN A
Protected
winding
IEC09000109-4-EN.vsd
M13048-8 v11
Application manual