ABB RELION 650 Series Applications Manual page 141

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
IEC06000557 V2 EN-US
Figure 65: For reverse power the set angle should be 180° in the overpower function
TripDelay1(2) is set in seconds to give the time delay for trip of the stage after pick up.
Hysteresis1(2) is given in p.u. of generator rated power according to equation 76.
=
S
3
N
EQUATION1708 V1 EN-US
The drop out power will be
The possibility to have low pass filtering of the measured power can be made as shown in the
formula:
= ×
S
k S
EQUATION1893 V1 EN-US
Where
S
S
old
S
Calculated
k
The value of
quite long.
The calibration factors for current and voltage measurement errors are set % of rated current/
voltage:
Application manual
Operate
Power 1(2)
×
×
UBase IBase
Power1(2) - Hysteresis1(2) .
(
)
+
-
×
1
k S
Old
Calculated
is a new measured value to be used for the protection function
is the measured value given from the function in previous execution cycle
is the new calculated value in the present execution cycle
is settable parameter
k = 0.92 is recommended in generator applications as the trip delay is normally
Q
o
Angle1(2 ) = 180
IEC06000557-2-en.vsd
Section 7
Current protection
P
(Equation 76)
(Equation 77)
135