1MRK 504 158-UEN A
Function n
IEC04000207 V2 EN-US
Figure 78: Application example showing a logic diagram for control of built-in functions
Device 1
IEC04000208 V2 EN-US
Figure 79: Application example showing a logic diagram for control of external devices
11.8.3

Setting guidelines

The parameters for Single command, 16 signals (SINGLECMD) are set via the local HMI or
PCM600.
Parameters to be set are MODE, common for the whole block, and CMDOUTy which includes
the user defined name for each output signal. The MODE input sets the outputs to be one of
the types Off, Steady, or Pulse.
Application manual
Single
command
function
SINGLECMD
CMDOUTy
OUTy
Single
command
function
SINGLESMD
CMDOUTy
OUTy
via configuration logic circuits
Function n
Configuration logic circuits
&
User-
defined
conditions
Section 11
Control
en04000207.vsd
en04000208.vsd
M12448-3 v2
179