Reactor Winding, Solidly Earthed - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 6
Differential protection
REFPDIF
I3PW1CT1
I3PW2CT1
IdN/I
IEC09000111-4-EN V2 EN-US
Figure 33: Connection of restricted earth fault, low impedance function REFPDIF for an
6.2.2.4

Reactor winding, solidly earthed

Reactors can be protected with restricted earth-fault protection, low impedance function
REFPDIF. The connection of REFPDIF for this application is shown in figure 34.
82
I3P
autotransformer, solidly earthed
-
Auto
transformer
IEC09000111-4-EN.vsd
1MRK 504 158-UEN A
HV (W1)
LV (W2)
M13048-18 v10
Application manual