Zero Clamping - ABB RELION 650 Series Applications Manual

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

Section 13
Monitoring
All measured values can be supervised with four settable limits that is, low-low limit, low limit,
high limit and high-high limit. A zero clamping reduction is also supported, that is, the
measured value below a settable limit is forced to zero which reduces the impact of noise in
the inputs.
Dead-band supervision can be used to report measured signal value to station level when
change in measured value is above set threshold limit or time integral of all changes since the
last time value updating exceeds the threshold limit. Measure value can also be based on
periodic reporting.
The measurement function, , provides the following power system quantities:
P, Q and S: three phase active, reactive and apparent power
PF: power factor
U: phase-to-phase voltage amplitude
I: phase current amplitude
F: power system frequency
,
The measuring functions CMMXU, VMMXU and VNMMXU provide physical quantities:
I: phase currents (amplitude and angle) (CMMXU)
U: voltages (phase-to-earth and phase-to-phase voltage, amplitude and angle) (VMMXU,
VNMMXU)
The function calculates three-phase power quantities by using fundamental frequency phasors
(DFT values) of the measured current respectively voltage signals. The measured power
quantities are available either, as instantaneously calculated quantities or, averaged values
over a period of time (low pass filtered) depending on the selected settings.
It is possible to calibrate the measuring function above to get better then class 0.5
presentation. This is accomplished by angle and amplitude compensation at 5, 30 and 100% of
rated current and at 100% of rated voltage.
The measuring functions CMSQI and VMSQI provide sequence component quantities:
I: sequence currents (positive, zero, negative sequence, amplitude and angle)
U: sequence voltages (positive, zero and negative sequence, amplitude and angle).
13.1.3

Zero clamping

The measuring functions, CVMMXN, CMMXU, VMMXU and VNMMXU have no interconnections
regarding any setting or parameter.
Zero clampings are also entirely handled by the
each of the functions. For example, the zero clamping of
VMMXU, zero clamping of I1 is handled by
Example how CVMMXN is operating:
200
The available measured values of an IED are depending on the actual hardware
(TRM) and the logic configuration made in PCM600.
The power system quantities provided, depends on the actual hardware, (TRM)
and the logic configuration made in PCM600.
ZeroDb for each and every signal separately for
U12 is handled by UL12ZeroDb in
IL1ZeroDb in CMMXU ETC.
1MRK 504 158-UEN A
GUID-8DABC3F5-6615-493C-B839-A5C557A2FAE8 v3
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ret650

Table of Contents