ABB RELION 650 Series Applications Manual page 171

Transformer protection version 2.1
Hide thumbs Also See for RELION 650 Series:
Table of Contents

Advertisement

1MRK 504 158-UEN A
QCBAY
IEC05000116 V1 EN-US
Figure 70: Signal flow between apparatus control function blocks
Accepted originator categories for PSTO
If the requested command is accepted by the authority, the value will change. Otherwise the
attribute
changed during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
Table 24: Accepted originator categories for each PSTO
Permitted Source To Operate
0 = Off
1 = Local
2 = Remote
3 = Faulty
4 = Not in use
5 = All
6 = Station
7 = Remote
Application manual
SCILO
SCILO
blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value is
SXCBR
SCSWI
SXCBR
SXCBR
SXSWI
SCSWI
Originator (orCat)
4,5,6
1,4,5,6
2,3,4,5,6
4,5,6
4,5,6
1,2,3,4,5,6
2,4,5,6
3,4,5,6
IEC 61850
-QB1
-QA1
-QB9
en05000116.vsd
Table 24
Section 11
Control
165