Beckhoff EL6601 Documentation page 93

Switch terminals for ethernet
Table of Contents

Advertisement

Index 1C32 SM output parameter (only with network variables)
Index (hex) Name
1C32:0
SM output parameter Synchronization parameters for the outputs
1C32:01
Sync mode
1C32:02
Cycle time
1C32:03
Shift time
1C32:04
Sync modes sup-
ported
Index 1C33 SM input parameter (only with network variables)
Index (hex) Name
1C33:0
SM input parameter
1C33:01
Sync mode
1C33:02
Cycle time
1C33:03
Shift time
1C33:04
Sync modes sup-
ported
EL6601, EL6614
Meaning
Current synchronization mode:
• 1: Synchronous with SM 2 event
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle time
• DC mode: SYNC0/SYNC1 Cycle Time
Time between SYNC0 event and output of the outputs (in
ns, DC mode only)
Supported synchronization modes:
• Bit 1 = 1: Synchron with SM 2 event is supported
Meaning
Synchronization parameters for the inputs
Current synchronization mode:
• 34: Synchron with SM 2 Event (outputs available)
as 0x1C32:02 [} 93]
Time between SYNC0 event and reading of the inputs (in
ns, only DC mode)
Supported synchronization modes:
• Bit 1: Synchronous with SM 2 Event is supported
(outputs available)
Version: 4.2
Commissioning
Data type
Flags
Default
UINT8
RW
0x0E (14
UINT16
RW
0x0001 (1
UINT32
RW
0x00000000
(0
)
dec
UINT32
RW
0x00000000
(0
)
dec
UINT16
RW
0x0002 (2
Data type
Flags
Default
UINT8
RW
0x0E (14
UINT16
RW
0x0022 (34
UINT32
RW
0x00000000
(0
)
dec
UINT32
RW
0x00000000
(0
)
dec
UINT16
RW
0x0002 (2
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
93

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El6614

Table of Contents