Beckhoff EL6601 Documentation page 83

Switch terminals for ethernet
Table of Contents

Advertisement

In general, an EtherCAT Slave offers
• communication diagnosis typical for a slave (diagnosis of successful participation in the exchange of
process data, and correct operating mode)
This diagnosis is the same for all slaves.
as well as
• function diagnosis typical for a channel (device-dependent)
See the corresponding device documentation
The colors in Fig. "Selection of the diagnostic information of an EtherCAT Slave" also correspond to the
variable colors in the System Manager, see Fig. "Basic EtherCAT Slave Diagnosis in the PLC".
Colour
Meaning
yellow
Input variables from the Slave to the EtherCAT Master, updated in every cycle
red
Output variables from the Slave to the EtherCAT Master, updated in every cycle
green
Information variables for the EtherCAT Master that are updated acyclically. This means that
it is possible that in any particular cycle they do not represent the latest possible status. It is
therefore useful to read such variables through ADS.
Fig. "Basic EtherCAT Slave Diagnosis in the PLC" shows an example of an implementation of basic
EtherCAT Slave Diagnosis. A Beckhoff EL3102 (2-channel analogue input terminal) is used here, as it offers
both the communication diagnosis typical of a slave and the functional diagnosis that is specific to a channel.
Structures are created as input variables in the PLC, each corresponding to the process image.
Fig. 105: Basic EtherCAT Slave Diagnosis in the PLC
EL6601, EL6614
Version: 4.2
Commissioning
83

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El6614

Table of Contents