52
Process Image
4.3.13.2

S5-FB250 Format

With the setting "Resistance measurement 1" (0 Ohm to 5.0 kOhm) and activated
S5-FB250 format, the I/O module outputs the measured resistance values of the
sensors directly.
The resistance values are displayed at a resolution of 1 digit per 4 Ohm. The status
information is depicted in bit 0 to bit 2 and the digitalized measured value in bit 3
to bit 15.

Table 43: ID 14, Setting "Resistance measurement 1", S5-FB250 Format

Resistance
Ω
0
100
200
300
1000
2000
3000
4000
5000
> 5000
Overrange
> 5010
Wire break
1) When short circuit and wire break monitoring is ON (see section "Diagnostics" > „Behavior in
the Event of an Error")
2) When underrange / overrange limit is ON (see section "Diagnostics" > „Behavior in the Event
of an Error")
3) Status information:
X: Not used,
F: Short circuit, wire break,
Ü: Underrange, overrange
4.3.14
Resistance Measurement 2, 0 Ohm ... 1.2 kOhm, ID 15
No short-circuit detection for resistance measurements!
For sensor types "Resistance measurement 1" and "Resistance measurement 2",
short-circuit detection is not technically possible.
4.3.14.1

Default Format

With the setting "Resistance measurement 2" (0 Ohm to 1.2 kOhm), the I/O
module outputs the measured resistance values of the sensors directly.
The resistance values are displayed at a resolution of 1 digit per 0.05 Ω in one
word (16-bit). The maximum number range viewable in one word in two's
Numeric value with status information
Binary
'0000.0000.0000.0 000'
'0000.0000.1100.1 000'
'0000.0001.1001.0 000'
'0000.0010.0101.1 000'
'0000.0111.1101.0 000'
'0000.1111.1010.0 000'
'0001.0111.0111.0 000'
'0001.1111.0100.0 000'
'0010.0111.0001.0 000'
'0010.0111.0001.0 001'
2)
'0010.0111.0001.0 010'
1)
XFÜ
Hex.
0x0000
0x00C8
0x0190
0x0258
0x07D0
0x0FA0
0x1770
0x1F40
0x2710
0x2711
0x2712
WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Status
3)
byte
hex.
Dec.
0
0x00
200
0x00
400
0x00
600
0x00
2000
0x00
4000
0x00
6000
0x00
8000
0x00
10000
0x00
10001
0x42
10002
0x60
Manual
Version 1.1.0
Error
LED
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON