WAGO-I/O-SYSTEM 750
750-451 8 AI RTD
Pos : 17.13 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Ansc hlüss e/Leistungs kontakte/F eldvers orgung - Ü berschrift 3 @ 6\mod_1256294692864_21.doc x @ 43664 @ 3 @ 1
3.2.2

Power Jumper Contacts/Field Supply

Pos : 17.14.1 /Serie 750 ( WAGO-I/O- SYST EM)/Wic htig e Erl äuter ung en/Sic her hei ts- und s onstige Hi nweise/Vorsicht/Vorsic ht: Verletzungsgefahr durc h sc har fkantige Mes ser kontakte! @ 6\mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
Pos : 17.14.2 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Ansc hlüss e/Leistungs kontakte 2 LK (M ess er/Leistungs kontakte 2 LK (Mess er/F eder) - Einl eitung @ 15\mod_1371721641099_21.doc x @ 123714 @ @ 1
The I/O module 750-451 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.
Pos : 17.14.3 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Ansc hlüss e/Leistungs kontakte 2 LK (M ess er/Feder) - Abbildung (16-Kanal) @ 15\mod_1370866610582_21.doc x @ 122222 @ @ 1

Figure 3: Power Jumper Contacts

Pos : 17.14.4 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Ansc hlüss e/Leistungs kontakte 2 LK (M ess er/Leistungs kontakte 2 LK (Mess er/F eder) - Leg ende @ 15\mod_1371721352500_21.doc x @ 123710 @ @ 1

Table 4: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Pos : 17.14.5 /Serie 750 ( WAGO-I/O- SYST EM)/Wic htig e Erl äuter ung en/Sic her hei ts- und s onstige Hi nweise/Ac htung/Ac htung: Maxi maler Str om Leis tungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos : 17.15 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.1.0
Type
Spring contact
Potential transmission (U
Spring contact
Potential transmission (0 V) for field supply
Blade contact
Blade contact
Function
Potential feed-in (0 V) for field supply
Potential feed-in (U
v
Device Description
) for field supply
v
) for field supply
17