36
Process Image
4.3.5.2

S5-FB250 Format

With the setting "Pt500 (IEC 751)" and activated S5-FB250 format, the I/O
module converts the measured resistance values of Pt500 sensors (IEC 751) into
temperature values and outputs the conversion results. The temperature values are
displayed at a resolution of 1 digit per 0.5 °C.
The status information is depicted in bit 0 to bit 2 and the digitalized measured
value in bit 3 to bit 15.

Table 27: ID 3, Setting Pt500 (IEC 751), S5-FB250 Format

Temperatur
e
°C
---
Short circuit
< −200.0
Underrange
−200.0
−100.0
0.0
100.0
200.0
500.0
750.0
800.0
850.0
> 850.0
Overrange
---
Wire break
1) Temperature values below 0 °C are represented in two's complement binary.
2) When short circuit and wire break monitoring is ON (see section "Diagnostics" > "Behavior in
the Event of an Error")
3) When underrange / overrange limit is ON (see section "Diagnostics" > "Behavior in the Event
of an Error")
4) Status information:
X: Not used,
F: Short circuit, wire break,
Ü: Underrange, overrange
Numeric value
Resistance
Ω
Binary
< 10.00
'1111.0011.1000.0 010'
2)
< 92.60
'1111.0011.1000.0 001'
3)
92.60
'1111.0011.1000.0 000'
301.28
'1111.1001.1100.0 000'
500.00
'0000.0000.0000.0 000'
692.53
'0000.0011.1110.1 000'
879.28
'0000.1100.1000.0 000'
1404.89
'0001.1111.0100.0 000'
1803.19
'0010.1110.1110.0 000'
1878.52
'0011.0010.0000.0 000'
1952.41
'0011.0101.0010.0 000'
> 1952.41
'0011.0101.0010.0 001'
3)
> 5010.00
'0011.0101.0010.0 010'
2)
WAGO-I/O-SYSTEM 750
1)
with status information
XFÜ
Hex.
Dec.
0xF382
−3198
0xF381
−3199
0xF380
−3200
0xF9C0
−1600
0x0000
0x0640
1600
0x0C80
3200
0x1F40
8000
0x2EE0
12000
0x3200
12800
0x3520
13600
0x3521
13601
0x3522
13602
750-451 8 AI RTD
Status
4)
Error
byte
LED
hex.
0x50
ON
0x41
ON
0x00
OFF
0x00
OFF
0
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x60
ON
Manual