WAGO-I/O-SYSTEM 750
750-451 8 AI RTD

Table 54: Register 41

Register
41
Bit 0 ... 15: User scaling Divisor
0 ... 65535
0000 ... FFFF
0 ... 65535
0000 ... FFFF
User scaling is enabled if bit 7 is set in register 35.
*) y1= unscaled process value
y2= scaled process value
**) Gain Divisor = set to 256 by default, cannot be changed
***)
This value cannot be changed

Table 55: Register 42

Register
42
Bit 0 ... 15: Lower user limit value
–32768 ... 32767
8000 ... 7FFF
Value range depending on the
sensor type set
(see chapter "Process Data"
"Overview of Sensor Types")
This register contains the lower user limit value. The resistance/temperature value calculated by the
I/O module is compared to the limiting value entered by the user. If the resistance/temperature
value calculated by the I/O module falls below the value entered here, the I/O modules signals a
limiting value underrange.
The scaling of the value to be entered here depends on the sensor type set.
Diagnostics for the lower user limit value is enabled if bit 10 in register 35 is set.
Manual
Version 1.1.0
Function
User scaling
Divisor
Value range (raw), decimal, 16-bit unsigned integer
Value range (raw), hexadecimal, 16-bit unsigned integer
Value range (scaled), decimal, 16-bit unsigned integer
Value range (scaled), hexadecimal, 16-bit unsigned integer
Resolution: 1
Unit
Equation*: y2 = ((y1 × Reg40) / 256**) + Reg39
Function
Lower user limit value
Value range (raw), decimal, 16-bit integer
Value range (raw), hexadecimal, 16-bit integer
Value range (scaled), decimal, 16-bit unsigned integer
Value range (scaled), hexadecimal, 16-bit unsigned integer
Resolution:
Unit
Memory
Access
EEPROM
R
Memory
Access
EEPROM
R/W
1
Commissioning
67
Default setting
0x0100***
Default setting
0x8000