3.9. Error Code

If the following errors occur, the reply command from the inverter is returned by adding 80H to the command
received by the inverter. The error codes are as follows.
Error code
01
Command error
02
Communication number error
03
04
Execution impossible
Name
• No command exists.
• The MEI type is not 14 (0x0E) with the model
• No communication number exists.
• Writing was performed to the exclusive reading
• Illegal Object ID with the model information reading by
• Data range error.
• The communication format has an error.
Data error
• When the reading equipment code is set to 4 or more
• Writing to parameter that is impossible to be written
• Writhing to parameter for which TYP is being
• Writing to [F738: Password setting] when [F738] is set.
Description
information reading by Modbus function code 0x2B.
parameter.
Modbus function code 0x2B.
in model information reading command.
while running.
executed.