Toshiba TOSVERT VF-AS3 Instruction Manual page 16

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

[C671: Emb Eth. Massage timeout detection time]
Adjustment range:
0: Disable
0.1-100.0 s
When you use the Massage service of ModbusTCP, inverter will detect the time out error if Massage is not
performed between periods of [C671] setting.
When [C671] is set to "0: Disable", timeout for Massage function does not detected.
Massage time out error is not detected during I/O scanning.
Assigning IP addresses parameters [C610], [C611] to [C622]
The following setting parameters can be accessed from the "Embedded Ethernet setting" on guidance
function. For detail of "Embedded Ethernet setting", refer to section "1.6 Setting IP address".
The address is assigned according to setting of [C610: Emb Eth. IP setting mode].
C610
0
The device uses the address defined in [C611] to [C622]
1
The device receives its address from a BOOTP server.
2
The device receives its address from a DHCP server.
When you set up the IP address by manual ([C610] = "0"), bellow parameters setting are needed.
[C611 to C614: Emb Eth. IP address setting value 1 to 4]
[C615 to C618: Emb Eth. Subnet mask setting value 1 to 4]
[C619 to C622: Emb Eth. Default gateway setting value 1 to 4]
These parameters are effective settings at [C610] = "0: Fixed").
If you set [C610] = "1: BOOTP" or "2: DHCP", these parameters are invalidity.
After dynamic addressing by BOOTP server or DHCP server, the new address values are displayed in the
bellow monitor parameters.
[C629 to C632: Emb Eth. IP address monitor 1 to 4]
[C633 to C636: Emb Eth. Subnet mask monitor 1 to 4]
[C637 to C640: Emb Eth. Default gateway monitor 1 to 4]