3.4. "03 (0x03) Read Holding Registers" function

This Modbus request is used to read a value continuously from contiguous inverter parameters.
Request Format:
Byte
0
Function Code = 0x03
1
Communication No. of Starting Parameter Hi
2
Communication No. of Starting Parameter Lo
3
Number of Parameters Hi (0)
4
Number of Parameters Lo (1 - 125)
Response format:
Byte
0
Function Code = 0x03
1
Byte Count (B = 2 × Number of Points)
2
First Parameter Data Hi
3
First Parameter Data Lo
・・・
・・・・・・・・・・・・・・・・
B
Last Parameter Data Hi
B+1
Last Parameter Data Lo
Exception response format:
Byte
0
Function Code = 0x83
Exception Code
1: Illegal Function
1
2: Illegal Data Address
3: Illegal Data Value
If the communication number that doesn't exist is read, device returns 0x8000.