Parameter setting example for embedded ethernet
Below setting example, the frequency reference and operation command are input from the panel of the
leader, and these are transmitted to the follower by inverter to inverter communication.
Parameters of the leader (examples)
[CMOd] = "1" Example: Operation panel
[FMOd] = "10" Example: Touch wheel 1
[C610] = "0" Fixed
[C611] = "192"
[C612] = "168"
[C613] = "1"
[C614] = "10"
[C611] = "255"
[C612] = "255"
[C613] = "255"
[C614] = "0"
[C680] = "1" Inverter to inverter communication
[C681] = "0" Leader
[C682] = "3" Leader (transmit frequency command)
Parameters of the followers (examples)
[CMOd] = "2" Embedded Ethernet
[FMOd] = "20" Embedded Ethernet
[C610] = "0"
[C611] = "192"
[C612] = "168"
[C613] = "1"
[C614] = "20"
[C611] = "255"
[C612] = "255"
[C613] = "255"
[C614] = "0"
[C680] = "1" Inverter to inverter communication
[C681] = "1" Follower 1
[C682] = "0" Follower (0Hz command when Leader fails)