Toshiba TOSVERT VF-AS3 Instruction Manual page 25

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

[FD00: Output frequency]
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is "80Hz", 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01Hz,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
- [FD16: Speed feedback frequency] ................................................ Unit: 0.01Hz
- [FD22: PID feedback value] ............................................................ Unit: 0.01Hz
- [FD29: Input power]......................................................................... Unit: 0.01kW
- [FD30: Output power] ...................................................................... Unit: 0.01kW
[FD03: Output current]
The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current is 2.4A with the rated current 4.8A, 0x1388 (50.00%) is read out.
Since the minimum unit is 0.01%,
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)
Also about the following parameters, these are the same as this.
- [FD04: Input voltage (DC detection)] .............................................. Unit: 0.01% (V)
- [FD05: Output voltage] .................................................................... Unit: 0.01% (V)
- [FD18: Torque] ................................................................................ Unit: 0.01% (Nm)*
* When the motor information are set to the parameter ([F405 to F415]), torque monitor value "100%" is
same as the rated torque of a motor in general.
[FE35, FE36, FE37: Monitoring of the analog input RR, RX, II]
[FE35: Terminal RR input value]
[FE36: Terminal RX input value]
[FE37: Terminal II input value]
These monitors can be used as A/D converter.
[FE35] and [FE37] are capable of reading the data from external devices in a range of 0.01 to 100.00%
(unsigned data: 0x0000 to 0x2710).
[FE36] is capable of reading the data from external devices in a range of -100.00 to 100.00% (signed data:
0xD8F0 to 0x2710).
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in
mind that any data entered via an analog terminal is regarded as a frequency command.
[FE14: Cumulative run time for monitor]
The operated cumulative time is read by the hexadecimal number.
For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read.
0x12 (Hex.) = 18 (Dec., hour)