Instance 100: Toshiba control output
Instance 100 mapping
Byte
Bit 7
Bit 6
AD mode 1/
0
DC braking
AD mode 2
1
Net Ctrl*
Net Ref *
2
3
* Bit 6 and 7 of the instance 100 byte 1 are defined as follows.
Bit 7 (Net Ctrl) ................. When "1" is set, all commands of byte 0 and 1 are enabled. When "0" is set,
Bit 6 (Net Ref) ................. When "1" is set,
**
Drive Reference Speed
For example, when "Frequency reference" is set up to 60Hz, since the minimum unit is 0.01Hz,
60 / 0.01 = 6000 = 0x1770
Instance 150: Toshiba control input
Instance 150 mapping
Byte
Bit 7
Bit 6
0
DC braking
AD mode
READY
HAND/AUTO
1
without
(LOC/REM)
ST/RUN
2
3
Bit 5
Bit 4
PID off
V/f switching
Emergency
Reset trip
stop
Drive Reference Speed Hz (Low byte) **
Drive Reference Speed Hz (High byte) **
commands other than Emergency stop and Reset trip are according to setup of
the parameter [CMOd].
Drive Reference Speed is according to bytes 2 and 3
Drive Reference Speed is according to setup of the parameter [FMOd].
is set up by 0.01Hz unit and the hexadecimal number.
Bit 5
Bit 4
PID
V/f 2
READY
Emergency
with
stopping
ST/ RUN
Drive Actual Speed Hz (Low byte)
Drive Actual Speed Hz (High byte)
Bit 3
Bit 2
Preset
Preset
Speed4
Speed3
Free run (ST)
Run/stop
Bit 3
Bit 2
MOFF
ALARM
Free run (ST)
Run/Stop
43
E6582125
Bit 1
Bit 0
Preset
Preset
Speed2
Speed1
Forward/
Jog run
Reverse
. When "0" is set,
Bit 1
Bit 0
EMG
FL
Forward /
Jog running
Reverse