Toshiba TOSVERT VF-AS3 Instruction Manual page 23

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

[FA37: Frequency command from embedded ethernet]
Setting range: "0" to [FH: Maximum frequency]
This frequency command value is enabled only when the frequency command via embedded ethernet is
enabled. To make frequency commands via embedded ethernet enabled, set [FMOd: Frequency
command select 1] to "20": Embedded Ethernet" or set the "Command priority" option (bit 14 of [FA36]).
Frequency command is set up by 0.01Hz unit and the hexadecimal number.
For example: when "Frequency command" is set up to "80Hz", since the minimum unit is 0.01Hz,
80Hz=80÷0.01 = 8000 (Dec.) = 0x1F40 (Hex.)
[FA40: Torque command setting from embedded ethernet]
Torque reference is set up by 0.01% unit and the hexadecimal number.
For example: when "torque command" is set up to "50%", since the minimum unit is 0.01%,
50%=50÷0.01=5000 (Dec.) =0x1388 (Hex.)
[FA50: Terminal output data]
By setting up the data of the bit 0 - 1 of [FA50] from communication, setting data (OFF or ON) can be
outputted to the output terminal.
Please select the functional number 92 - 95 as the selection of the output terminal function [F130 to F138]
before using it.
bit
Output TB function name
Designated data output
0
(Output terminal No.: 92, 93)
Designated data
1
(Output terminal No.: 94, 95)
2-15
(Reserved)
Note: Set 0 to reserved bit
1
output 2
21
E6582125
0
1
OFF
ON
OFF
ON
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents