06 (0X06) Write Single Register" Function - Toshiba TOSVERT VF-AS3 Instruction Manual

Embedded ethernet function
Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

3.5. "06 (0x06) Write Single Register" function

This Modbus request is used to write the value to the inverter parameter.
Request format:
Byte
0
Function Code = 0x06
1
Communication No. of Parameter Hi
2
Communication No. of Parameter Lo
3
Write Data Hi
4
Write Data Lo
Response format:
Byte
0
Function Code = 0x06
1
Communication No. of Parameter Hi
2
Communication No. of Parameter Lo
3
Write Data Hi
4
Write Data Lo
Exception response format:
Byte
0
Function Code = 0x86
Exception Code
1: Illegal Function
1
2: Illegal Data Address
3: Illegal Data Value
4: Slave Device Failure
When you use this Modbus request, the value is written to the EEPROM.
Meaning
Meaning
Meaning
Notes
28