Subfault: 33.11
Description: Hardware compatibility error
Response: Output stage inhibit
Firmware does not match device.
Subfault: 33.12
Description: Memory module plugged in
Response: Output stage inhibit
System state: Fault acknowledgment with CPU reset
A plugged-in memory module was detected dur-
ing device start. The setting for the device para-
meter source is set to "Internal memory".
Subfault: 33.13
Description: Memory module removed
Response: Output stage inhibit
System state: Fault acknowledgment with CPU reset
The device was started without a memory
module. The setting for the device parameter
source is set to "Replaceable memory module".
Replaceable memory module removed during on-
going operation.
Subfault: 33.14
®
Description: EtherCAT
Response: Output stage inhibit
System state: Fault acknowledgment with CPU reset
®
The EtherCAT
slave controller cannot be ad-
dressed.
Cause
Cause
Cause
slave controller cannot be accessed
Cause
Fault table CiA402 profile
Measure
Contact SEW-EURODRIVE Service.
Measure
– Switch off the device. Remove the memory
module and restart the device.
– Change the parameter "Non-volatile memory
source" to "Arbitrary" or "Replaceable memory
module". Switch the device off and on again.
Measure
Switch off the device. Insert the memory module
and restart the device.
Change the parameter "Non-volatile memory
source" to "Internal memory". Switch the device
off and on again.
Measure
Contact SEW-EURODRIVE Service.
Operating Instructions – MOVIGEAR
Service
8
265
®
performance
Need help?
Do you have a question about the Movigear Performance MGF**-DFC-C Series and is the answer not in the manual?