7
DynaStop® in conjunction with STO
7.5.2
Behavior when STO is activated before standstill (rotational speed = 0)
146
Operating Instructions – MOVIGEAR
NOTICE
Depending on the settings of parameter "8501.3, bit  0 "Apply brake/DynaStop
STO state", the DynaStop
ted operating range.
This can cause a high torque load/high motor currents, which may damage the drive
unit and the application.
Use the factory settings or recommended settings.
If STO is activated before the motor has come to standstill, the DynaStop
haves as set in parameter Parameter 8501.3, bit  0 "Apply brake/DynaStop
state":
Parameter 8501.3, bit 0 "Apply brake/DynaStop
®
DynaStop
is activated when STO is triggered.
Parameter 8501.3, bit 0 "Apply brake/DynaStop
(Factory setting/recommended setting)
®
The DynaStop
status remains unchanged when STO is triggered.
Depending on the application, the motor coasts to a halt or even accelerates.
The stopping distance is not defined.
®
performance
®
function can be activated at values outside of the permit-
®
in STO state" = 1 = YES
®
in STO state" = 0 = NO
®
in
®
function be-
®
in STO