Equation 23: Report Tbl If Stair Press Fan Not On; Equation 24: Report Tbl If Stair Press Fan Not Off; Equation 25: Report Tbl If Main Exh Damper Not Open; Equation 26: Report Tbl If Main Exh Damper Not Closed - Simplex 4100U Application Manual

Smoke management
Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Smoke Control System Custom Control Equations,
Equation 23:
Report TBL if Stair
Press Fan Not ON
Equation 24:
Report TBL if Stair
Press Fan Not OFF
Equation 25:
Report TBL if
Main EXH Damper
Not Open
Equation 26:
Report TBL if
Main EXH Damper
Not Closed
Label: REPORT TBL IF STAIR PRESS FAN NOT ON
COMMENTS:
INPUTS:
The ON state of:
M1-9
CPRESS
STAIR PRESS FAN
DELAY for 10 sec., running timer is A265
AND NOT the ON state of:
M1-42
UTILITY
MONITOR STAIR PRESS FAN ON
OUTPUTS:
HOLD points ON pri=9,9
P280
UTILITY
STAIR PRESS FAN FAIL
END:
Label: REPORT TBL IF STAIR PRESS FAN NOT OFF
COMMENTS:
INPUTS:
NOT the ON state of:
M1-9
CPRESS
STAIR PRESS FAN
DELAY for 10 sec., running timer is A290
AND NOT the ON state of:
M1-47
UTILITY
MONITOR STAIR PRESS FAN OFF
OUTPUTS:
HOLD points ON pri=9,9
P280
UTILITY
STAIR PRESS FAN FAIL
END:
Label: REPORT TBL IF MAIN EXH DAMPER NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-13
CDAMPER
MAIN EXHAUST AIR DAMPER
DELAY for 10 sec., running timer is A262
AND NOT the ON state of:
M1-51
UTILITY
MONITOR MAIN EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P272
UTILITY
MAIN EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF MAIN EXH DAMPER NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-13
CDAMPER
MAIN EXHAUST AIR DAMPER
DELAY for 10 sec., running timer is A281
AND NOT the ON state of:
M1-52
UTILITY
MONITOR MAIN EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P272
UTILITY
MAIN EXHAUST AIR DAMPER FAIL
END:
Continued
Equation 23
Equation 24
5-16
Equation 25
Equation 26