Smoke Control System Custom Control Equations,
Equation 59:
Control EXH Air
Damper 3 Open
Equation 60:
Manual Control EXH
Air Damper 3 Close
Equation 61:
Manual Control EXH
Air Damper 4 Open
Equation 62:
Manual Control EXH
Air Damper 4 Close
Label: MANUAL CONTROL EXH AIR DAMPER 3 OPEN
COMMENTS:
INPUTS:
The UP state of:
8-71
SWITCH
Ann 1 Pt 71 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points ON pri=5,9
M1-21
CDAMPER
3RD FLOOR EXHAUST/RETURN AIR DAMPER
END:
Label: MANUAL CONTROL EXH AIR DAMPER 3 CLOSE
COMMENTS:
INPUTS:
The DOWN state of:
8-71
SWITCH
Ann 1 Pt 71 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points OFF pri=5,9
M1-21
CDAMPER
3RD FLOOR EXHAUST/RETURN AIR DAMPER
END:
Label: MANUAL CONTROL EXH AIR DAMPER 4 OPEN
COMMENTS:
INPUTS:
The UP state of:
8-73
SWITCH
Ann 1 Pt 73 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points ON pri=5,9
M1-22
CDAMPER
4TH FLOOR EXHAUST/RETURN AIR DAMPER
END:
Label: MANUAL CONTROL EXH AIR DAMPER 4 CLOSE
COMMENTS:
INPUTS:
The DOWN state of:
8-73
SWITCH
Ann 1 Pt 73 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points OFF pri=5,9
M1-22
CDAMPER
4TH FLOOR EXHAUST/RETURN AIR DAMPER
END:
Continued
5-25
Equation 59
Equation 60
Equation 61
Equation 62