Like smoke dampers, fan control and overriding the HVAC control is a basic function of the
Simplex Smoke Control System. General principles for interconnection to a non-dedicated fan are
shown in Figures 4-8 and 4-9.
In a non-dedicated fan control application, a 4090-9120 6-Point I/O Module is used to provide
inputs to a fan controller for smoke control override and monitor the feedback from the controller.
The wiring between the module and the fan controller is unsupervised, so the module must be
mounted within three feet of the controller in accordance with NFPA 72.
0V
+24V
FROM
FACP
INPUT 1
Figure 4-8. Non-Dedicated Fan Control Using a 6-Point I/O Module
1A @ 30 VDC
or
1/4 A @ 120 VAC
COMM
N/O
COMM
N/O
FA
RETURN
4-13
Continued
POWER
SOURCE
LISTED
RELAY
(N/O)
LISTED
RELAY
(N/C)
SERVICE
DISCONNECT
LISTED
SAIL
SWITCH
N
N/O
COMM
6.8 K 1/2 W EOLR
(Per Installation Instructions, 574-876)