Equation 3: Test Stairwell Air Pressure - Simplex 4100U Application Manual

Smoke management
Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Dedicated Smoke Control System Weekly Self-Test,
Equation 3:
Test Stairwell
Air Pressure
Equation 4:
Reset Stair Pressure
Fan to OFF
Equation 5:
End of Program
Label: TEST STAIRWELL AIR PRESSURE
COMMENTS:
INPUTS:
The ON state of:
P281
UTILITY
START SELF TEST PROGRAM
AND the ON state of:
M1-9
CPRESS
STAIR PRESS FAN
DELAY for 10 secs, running timer is A283
AND NOT the ON state of:
M1-42
UTILITY
MONITOR STAIR PRESS FAN ON
OUTPUTS:
HOLD points ON pri=9,9
P280
UTILITY
STAIR PRESS FAN FAIL
END:
Label: RESET STAIR PRESSURE FAN TO OFF
COMMENTS:
INPUTS:
The ON state of:
P281
UTILITY
START SELF TEST PROGRAM
AND the ON state of:
M1-9
CPRESS
STAIR PRESS FAN
DELAY for 60 secs, running timer is A284
OUTPUTS:
HOLD points OFF pri=9,9
M1-9
CPRESS
STAIR PRESS FAN
P281
UTILITY
START SELF TEST PROGRAM
PRINT to All ports/logs/displays
"SELF TEST PROGRAM IS COMPLETE"
END:
Label: [END-OF-PROGRAM]
Continued
Equation 3
Equation 4
Equation 5
5-4