Equation 39: Report Tbl If Exh Damper 1 Not Open; Equation 40: Report Tbl If Exh Damper 1 Not Closed; Equation 41: Report Tbl If Exh Damper 2 Not Open - Simplex 4100U Application Manual

Smoke management
Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Smoke Control System Custom Control Equations,
Equation 39:
Report TBL if EXH
Damper 1 Not Open
Equation 40:
Report TBL If EXH
Damper 1 Not
Closed
Equation 41:
Report TBL If EXH
Damper 2 Not Open
Equation 42:
Report TBL If
EXH Damper 2
Not Closed
Label: REPORT TBL IF EXH DAMPER 1 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-19
CDAMPER
1ST FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A258
AND NOT the ON state of:
M1-33
UTILITY
MONITOR FLR 1 EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P264
UTILITY
FL1 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 1 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-19
CDAMPER
1ST FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A276
AND NOT the ON state of:
M1-37
UTILITY
MONITOR FLR 1 EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P264
UTILITY
FL1 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 2 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-20
CDAMPER
2ND FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A277
AND NOT the ON state of:
M1-34
UTILITY
MONITOR FLR 2 EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P265
UTILITY
FL2 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 2 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-20
CDAMPER
2ND FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A259
AND NOT the ON state of:
M1-38
UTILITY
MONITOR FLR 2 EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P265
UTILITY
FL2 EXHAUST AIR DAMPER FAIL
END:
Continued
Equation 39
Equation 40
Equation 41
Equation 42
5-20