Smoke Control System Custom Control Equations,
Equation 43:
Report TBL If EXH
Damper 3 Not Open
Equation 44:
Report TBL If
EXH Damper 3
Not Closed
Equation 45:
Report TBL If EXH
Damper 4 Not Open
Equation 46:
Report TBL If
EXH Damper 4
Not Closed
Label: REPORT TBL IF EXH DAMPER 3 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-21
CDAMPER
3RD FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A278
AND NOT the ON state of:
M1-35
UTILITY
MONITOR FLR 3 EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P266
UTILITY
FL3 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 3 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-21
CDAMPER
3RD FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A260
AND NOT the ON state of:
M1-39
UTILITY
MONITOR FLR 3 EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P266
UTILITY
FL3 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 4 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-22
CDAMPER
4TH FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A279
AND NOT the ON state of:
M1-36
UTILITY
MONITOR FLR 4 EXHAUST AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P267
UTILITY
FL4 EXHAUST AIR DAMPER FAIL
END:
Label: REPORT TBL IF EXH DAMPER 4 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-22
CDAMPER
4TH FLOOR EXHAUST/RETURN AIR DAMPER
DELAY for 10 sec., running timer is A261
AND NOT the ON state of:
M1-40
UTILITY
MONITOR FLR 4 EXHAUST AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P267
UTILITY
FL4 EXHAUST AIR DAMPER FAIL
END:
Continued
Equation 43
Equation 44
Equation 45
Equation 46
5-21