Equation 31: Report Tbl If Sup Damper 1 Not Open; Equation 33: Report Tbl If Sup Damper 2 Not Open - Simplex 4100U Application Manual

Smoke management
Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Smoke Control System Custom Control Equations,
Equation 31:
Report TBL If SUP
Damper 1 Not Open
Equation 32:
Report TBL If
SUP Damper 1
Not Closed
Equation 33:
Report TBL If SUP
Damper 2 Not Open
Equation 34:
Report TBL If
Sup Damper 2
Not Closed
Label: REPORT TBL IF SUP DAMPER 1 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-15
CDAMPER
1ST FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A257
AND NOT the ON state of:
M1-25
UTILITY
MONITOR FLR 1 SUPPLY AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P260
UTILITY
FL1 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 1 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-15
CDAMPER
1ST FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A282
AND NOT the ON state of:
M1-29
UTILITY
MONITOR FLR 1 SUPPLY AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P260
UTILITY
FL1 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 2 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-16
CDAMPER
2ND FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A270
AND NOT the ON state of:
M1-26
UTILITY
MONITOR FLR 2 SUPPLY AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P261
UTILITY
FL2 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 2 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-16
CDAMPER
2ND FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A271
AND NOT the ON state of:
M1-30
UTILITY
MONITOR FLR 2 SUPPLY AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P261
UTILITY
FL2 SUPPLY AIR DAMPER FAIL
END:
Continued
Equation 31
Equation 32
Equation 33
Equation 34
5-18