Smoke Control System Custom Control Equations,
Equation 5:
Initialize Normal
Conditions at Reset
Equation 6:
Normal Conditions
Complete After
Reset
Label: INITIALIZE NORMAL CONDITIONS AT RESET
COMMENTS:
INPUTS:
The ON state of:
P290
UTILITY
SET NORMAL CONDITIONS AT RESET
AND NOT the TROUBLE state of:
P256
TROUBLE
FSCS SWITCHES NOT RESET
OUTPUTS:
HOLD points OFF pri=7,9
P275
UTILITY
SMOKE CONTROL ALARM INITIATE
P276
UTILITY
SMOKE CONTROL ZONE 1 INITIATE
P277
UTILITY
SMOKE CONTROL ZONE 2 INITIATE
P278
UTILITY
SMOKE CONTROL ZONE 3 INITIATE
P279
UTILITY
SMOKE CONTROL ZONE 4 INITIATE
HOLD points ON pri=9,9
M1-10
CPRESS
SUPPLY FAN RELAY
M1-11
CPRESS
EXHAUST FAN RELAY
M1-12
CDAMPER
MAIN OUTSIDE AIR DAMPER
M1-13
CDAMPER
MAIN EXHAUST AIR DAMPER
M1-14
CDAMPER
MAIN RETURN AIR DAMPER
M1-15
CDAMPER
1ST FLOOR SUPPLY AIR DAMPER
M1-16
CDAMPER
2ND FLOOR SUPPLY AIR DAMPER
M1-17
CDAMPER
3RD FLOOR SUPPLY AIR DAMPER
M1-18
CDAMPER
4TH FLOOR SUPPLY AIR DAMPER
M1-19
CDAMPER
1ST FLOOR EXHAUST/RETURN AIR DAMPER
M1-20
CDAMPER
2ND FLOOR EXHAUST/RETURN AIR DAMPER
M1-21
CDAMPER
3RD FLOOR EXHAUST/RETURN AIR DAMPER
M1-22
CDAMPER
4TH FLOOR EXHAUST/RETURN AIR DAMPER
HOLD points OFF pri=9,9
M1-9
CPRESS
STAIR PRESS FAN
END:
Label: NORMAL CONDITIONS COMPLETE AFTER RESET
COMMENTS:
INPUTS:
The ON state of:
P290
UTILITY
SET NORMAL CONDITIONS AT RESET
AND NOT the TROUBLE state of:
P256
TROUBLE
FSCS SWITCHES NOT RESET
DELAY for 10 sec., running timer is A294
OUTPUTS:
HOLD points OFF pri=9,9
P290
UTILITY
SET NORMAL CONDITIONS AT RESET
END:
Continued
Equation 5
5-9