Smoke Control System Custom Control Equations,
Equation 71:
Manual Control
Main SUP Air
Damper Open
Equation 72:
Manual Control
Main Sup Air
Damper Close
Equation 73:
Manual Control
Main EXH Air
Damper Open
Equation 74:
Manual Control
Main EXH Air
Damper Close
Label: MANUAL CONTROL MAIN SUP AIR DAMPER OPEN
COMMENTS:
INPUTS:
The UP state of:
8-77
SWITCH
Ann 1 Pt 77 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points ON pri=8,9
M1-12
CDAMPER
MAIN OUTSIDE AIR DAMPER
END:
Label: MANUAL CONTROL MAIN SUP AIR DAMPER CLOSE
COMMENTS:
INPUTS:
The DOWN state of:
8-77
SWITCH
Ann 1 Pt 77 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points OFF pri=8,9
M1-12
CDAMPER
MAIN OUTSIDE AIR DAMPER
END:
Label: MANUAL CONTROL MAIN EXH AIR DAMPER OPEN
COMMENTS:
INPUTS:
The UP state of:
8-78
SWITCH
Ann 1 Pt 78 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points ON pri=8,9
M1-13
CDAMPER
MAIN EXHAUST AIR DAMPER
END:
Label: MANUAL CONTROL MAIN EXH AIR DAMPER CLOSE
COMMENTS:
INPUTS:
The DOWN state of:
8-78
SWITCH
Ann 1 Pt 78 Graphic LED/SW Ctlr w/32
AND the ON state of:
P273
UTILITY
MASTER KEY SWITCH ENABLE
OUTPUTS:
HOLD points OFF pri=8,9
M1-13
CDAMPER
MAIN EXHAUST AIR DAMPER
END: