Advertisement

Smoke Control System Custom Control Equations,
Equation 35:
Report TBL If SUP
Damper 3 Not Open
Equation 36:
Report TBL If
SUP Damper 3
Not Closed
Equation 37:
Report TBL If SUP
Damper 4 Not Open
Equation 38:
Report TBL If
SUP Damper 4
Not Closed
Label: REPORT TBL IF SUP DAMPER 3 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-17
CDAMPER
3RD FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A272
AND NOT the ON state of:
M1-27
UTILITY
MONITOR FLR 3 SUPPLY AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P262
UTILITY
FL3 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 3 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-17
CDAMPER
3RD FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A273
AND NOT the ON state of:
M1-31
UTILITY
MONITOR FLR 3 SUPPLY AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P262
UTILITY
FL3 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 4 NOT OPEN
COMMENTS:
INPUTS:
The ON state of:
M1-18
CDAMPER
4TH FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A274
AND NOT the ON state of:
M1-28
UTILITY
MONITOR FLR 4 SUPPLY AIR DAMPER OPEN
OUTPUTS:
HOLD points ON pri=9,9
P263
UTILITY
FL4 SUPPLY AIR DAMPER FAIL
END:
Label: REPORT TBL IF SUP DAMPER 4 NOT CLOSED
COMMENTS:
INPUTS:
NOT the ON state of:
M1-18
CDAMPER
4TH FLOOR SUPPLY AIR DAMPER
DELAY for 10 sec., running timer is A275
AND NOT the ON state of:
M1-32
UTILITY
MONITOR FLR 4 SUPPLY AIR DAMPER CLOSED
OUTPUTS:
HOLD points ON pri=9,9
P263
UTILITY
FL4 SUPPLY AIR DAMPER FAIL
END:
Continued
Equation 35
Equation 36
Equation 37
Equation 38
5-19