120 •
MODBUS Functions
Internal Variables
Register address 0x2030 (MODBUS Address 408241, with a word count of upto 65)
Designation
Access
Description
Register address 0x2040 (MODBUS Address 408257)
Designation
Access
Description
4.2.5.4 Firmware Information
The following registers contain information on the firmware of the coupler:
Register address 0x2010 (MODBUS Address 408209, with a word count of 1)
Designation
Access
Description
Register address 0x2011 (MODBUS Address 408210, with a word count of 1)
Value
Access
Description
Description of the connected I/O modules
Read modules 0 ... 64
Length 1-65 words
These 65 registers identify the coupler and the first 64 modules present in a
node. Each module is represented in a word. Because item numbers cannot
be read out of digital modules, a code is displayed for them, as defined
below:
Bit position 0
->
Bit position 1
->
Bit position 2-7
->
Bit position 8-14
->
Bit position 15
->
Examples:
4 Channel Digital Input Module = 0x8401
bit
15
14 13 12 11 10 9
code
1
0 0 0 0
hex
8
2 Channel Digital Output Module = 0x8202
bit
15 14 13 12 11 10 9
code
1 0 0
0
0
hex
8
Implement a software reset
write (Write sequence 0xAA55 or 0x55AA)
With Writing 0xAA55 or 0x55AA the register will be reset.
Revision, INFO_REVISION
Read
Firmware Index, e. g. 0005 for version 5
Series code, INFO_SERIES
Read
WAGO serial number, e. g. 0750 for WAGO-I/O-SYSTEM 750
Input module
Output module
not used
module size in bits
Designation digital module
8
7
6
5
1
0
0
0
0
4
0
8
7
6
5
0
1
0
0
0
2
0
WAGO-I/O-SYSTEM 750
4
3
2 1 0
0
0
0
0 0
1
1
4
3
2 1 0
0
0
0
0 1
0
2
ETHERNET TCP/IP