WAGO 750 Series Manual page 60

Ethernet tcp/ip
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

54 • Fieldbus coupler 750-342
Starting up a Fieldbus Node
Note
The IP address can be allocated under other operating systems (i.e. under
Linux) as well as with any other BootP servers.
Attention
The IP address can be allocated in a direct connection via a crossover cable or
via a parallel cable and a hub. An allocation over a switch is not possible.
BootP table
Attention
Prerequisite for the following steps is the correct installation of the WAGO
BootP server.
1. Go to the Start menu, menu item Programs / WAGO Software / WAGO
BootP Server and click on WAGO BootP Server configuration.
An editable table will appear: "bootptab.txt".
This table displays the data basis for the BootP server. Directly following
the list of all notations used in the BootP table there are two examples for
the allocation of an IP address.
"Example of entry with no gateway" and "Example of entry with
gateway".
Fig. 3.1-11: BootP table
The examples mentioned above contain the following information:
Declaration
Meaning
node1,
Any name can be given for the node here.
node2
ht=1
Specify the hardware type of the network here.
The hardware type for ETHERNET is 1.
(The numbers are described in RFC1700)
ha=0030DE000100
Specify the hardware address or the MAC-ID of the ETHERNET
ha=0030DE000200
fieldbus coupler (hexadecimal).
ip= 10.1.254.100
Enter the IP address of the ETHERNET fieldbus coupler (decimal)
ip= 10.1.254.200
here.
T3=0A.01.FE.01
Specify the gateway IP address here.
Write the address in hexadecimal form.
sm=255.255.0.0
In addition enter the Subnet-mask of the subnet (decimal), where the
ETHERNET fieldbus coupler belongs to.
p012908e
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-342

Table of Contents