Marking The Location Of The Rail-Fixing Cage Nuts; Marking The Location Of The Mcu-Fixing Cage Nuts - Avaya Scopia Elite 6000 MCU Series Rack Mounting Manual

Table of Contents

Advertisement

Setting up the Device

Marking the location of the rail-fixing cage nuts

About this task
This procedure explains how to mark the location of the cage nuts serving to secure the rails to the
rack by means of screws.
Procedure
1. Read the mounting prerequisites, which contain important positioning and spacing
information..
2. Prepare masking tape or a felt-tip pen to mark the location of the cage nuts. If the holes on
the rack are marked with numbers, write down the numbers on a piece of paper.
3. Mark the location of the bottom cage nut on each post, starting with the left one. Place the
mark on the outer side of the post.
The mark must be beside the lower square hole from a pair of squares on the post.
Important:
CAUTION - The markings on the left and right posts must be at exactly the same height
to ensure the MCU is positioned horizontally in the rack.
Important:
As the top cage nuts are located right above the bottom cage nuts, there is no need to
mark their location.
Related links
Mounting the Device on to the Rack

Marking the location of the MCU-fixing cage nuts

About this task
There is an extra pair of cage nuts for each front-facing rack post. You need these cage nuts to fix
the MCU front panel to the post.
Procedure
1. From inside the front-facing rack post, mark the location of the lower MCU-fixing cage nut. It
must be aligned with the rail's top cage nut.
2. Count 4 square holes up. At the 4th hole mark the location of the upper MCU-fixing cage nut.
3. Repeat this procedure for the other front-facing post.
Related links
Mounting the Device on to the Rack
January 2017
on page 17
on page 17
Rack Mounting Guide for Avaya Scopia Elite 6000 MCU
Comments on this document? infodev@avaya.com