Commissioning A Smoke Sensor (Connected To The Ai/Di Port On The Skylight Actuator) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
5.
Step 2 Check the monitoring functions of smoke sensor.
Table 5-25 Commissioning the sensor
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End
5.7.2.2 Commissioning a Smoke Sensor (Connected to the AI/DI port on the
skylight actuator)
If a smoke sensor is installed, perform the following steps to configure it.
Context
Procedure
Step 1 Set smoke sensor parameters.
1.
2.
3.
Step 2 Check the monitoring functions of smoke sensor.
Issue 02 (2019-02-28)
Check that AI/DI_1 sensor type is set to Smoke sensor or Smoke sensor(NC). Ensure
that AI/DI_1 power supply is Yes, and click Submit.
The smoke sensor is connected to the AI/DI_1 on the FusionModule800 and AI/DI_1 sensor type needs
to be set to NO because of the cables configuration and that the ECC800 cannot identify the sensor type.
Normal Connection Status
Smoke sensor AI/DI_1 DI
alarm is displayed on the active
alarm page of the app or WebUI.
If the sensor is prefabricated, only check its settings.
The actual value prevails. Only the method of the parameter settings is described.
In this example, the smoke sensor is connected to the AI/DI_1 port on the skylight actuator.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Aisle > Skylight Actuator Group > Skylight Actuator 1 >
Running Parameters.
Set DI1 alarm level to Low voltage alarm or High voltage alarm, and click Submit.
Set DI1 alarm level to Low voltage alarm if the smoke sensor is connected over NO.
Set DI1 alarm level to High voltage alarm if the smoke sensor is connected over NC.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Alarm Clearance Method
If AI/DI_1 sensor type is set
to Smoke sensor, power off
and reset the smoke sensor to
clear the alarm.
If AI/DI_1 sensor type is set
to Smoke sensor(NC), press
the reset button of the smoke
sensor to clear the alarm.