ECC800 Data Center Controller
User Manual
Path
3.
4.
----End

5.3.15 Setting and Adding a PMAC615 AC Meter

Prerequisites
The model of the single-phase AC meter for the lighting control box is PMAC615.
In this example, a straight-through cable is used to connect the PMAC615 to the COM3 port
on the ECC800.
Procedure
Step 1 Set the PMAC615 communications address.
1.
2.
Issue 02 (2019-02-28)
Parameter
Name
Device address
Click Connect Test to check whether the PMAC625 connects to the ECC800 properly.
If the PMAC625 connects to the ECC800 properly, click Add Device.
If the PMAC625 does not connect to the ECC800 properly, check whether the cable
between the PMAC625 and the ECC800 is connected properly, whether the
PMAC625 and ECC800 are running properly, and whether the input parameters are
consistent with the PMAC625 parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter_device position.
After the PMAC615 is started, press
screen is displayed. Press
communications address setting screen.
Press
and a blinking cursor is displayed. Press
communications address (ranging from 1 to 247). Then press
address setting.
Figure 5-8 PMAC615 communications address
Copyright © Huawei Technologies Co., Ltd.
Setting
In this example, Device address is set to 100.
During actual configuration, set the device address
for the PMAC625 based on the actual situation.
on the displayed screen and the configuration
until the ID prompt is displayed, indicating the
5 Power-On Commissioning
to modify the
to confirm the
110