Setting And Adding An Smart Cooling Product - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
3.
----End

5.3.18 Setting and Adding an Smart Cooling Product

Context
In this example, the smart cooling product is connected to the COM1 port on the ECC800.
Procedure
Step 1 Set monitoring parameters for the smart cooling product.
1.
2.
3.
4.
Step 2 Add the smart cooling product.
1.
2.
Table 5-17 Setting parameters for the smart cooling product
Path
Issue 02 (2019-02-28)
Click Connect Test to check whether the independent deployment AI/DI unit connects
to the ECC800 properly.
a.
If the independent deployment AI/DI unit connects to the ECC800 properly, click
Add Device.
b.
If the independent deployment AI/DI unit does not connect to the ECC800 properly,
check whether the cable between the independent deployment AI/DI unit and the
ECC800 is connected properly, whether the independent deployment AI/DI unit and
ECC800 are running properly, and whether the input parameters are consistent with
the parameters of the independent deployment AI/DI unit.
Set the communications address on the controller screen of the smart cooling product.
Press Prg/mute and Set simultaneously for 5s until 0 is displayed on the controller
screen. Enter the correct password 77 by pressing the up and down keys, and press Set to
confirm the setting.
The controller provides three groups of parameters: Group 1 consists of St1 and St2 which specify
the cooling and heating thresholds. Group 2 consists of P-type parameters which are common
parameters that can be accessed without entering a password. Group 3 consists of C-type
configuration parameters that can be accessed only after the factory password is entered.
The communications address of the smart cooling product is a C-type parameter. After you enter the
correct password, C0 is displayed on the controller screen.
Set the parameter to C32 by pressing the up and down keys, and press Set to confirm the
setting.
Set the value of C32 to 1 by pressing the up and down keys, and press Set to confirm the
setting.
C32 indicates the serial port address.
The communications address can be set to a value in the range of 1–207.
Press Prg/mute for 5s to save the parameter setting and go back to the home screen.
Log in to the ECC800 WebUI as an administrator.
Add the smart cooling product.
Parameter
Name
Copyright © Huawei Technologies Co., Ltd.
Setting
5 Power-On Commissioning